Purge, proving and ignition in a fixed sequence.
Dual fuel & gas train
Gas and oil trains that deliver fuel to the burners safely, at the right pressure, with proving before every start.
- Fuels: NG / LPG · LDO / FO
- Safety: Double shut-off + proving
- Changeover: Purge, then switch
- Control: Burner management PLC
Overview
Every burner needs a fuel train: isolation, filtering, pressure regulation, two automatic shut-off valves, pressure switches and gauges, and on larger burners valve proving. On oil, a pump set, filter, heater for heavy oil and solenoid valves do the same job.
SHIVAS lays out the trains on a common skid, sized for the furnace rating, and ties them into the burner management system so a fault shuts fuel off and holds it off until reset.
Why it pays
Regulators sized for the burner demand.
Skid-mounted, isolatable, labelled.
Gas and oil lines side by side.
Technical specification
Typical ranges. Every unit is sized to your duty; the offer carries the exact figures.
| Gas | Isolation valve, filter, regulator, double shut-off, pressure switches, gauges |
|---|---|
| Oil | Pump set, filter, heater (FO), solenoid valves |
| Proving | Valve proving or pressure proving |
| Mounting | Common skid near the furnace |
Calculator
Work it out for your own plant. Every input is a typical value you can change and the results follow as you type; send the result to us and we reply with a proposal.
How it works
Dual fuel & gas train
Watch it run →One burner fires gas or oil. Each fuel has its own train of isolation, filtration, pressure control and safety shut-off valves, and every changeover starts with an air purge.
Shown running as: Gas · Oil
Main parts
- 1Manual ball valveIsolation for maintenance.
- 2Gas filterKeeps dirt out of the valves.
- 3Pressure gaugeInlet pressure at a glance.
- 4Pressure regulatorHolds a steady gas pressure to the burner.
- 5Low gas pressure switchTrips the burner if supply pressure falls.
- 6Safety shut-off valve 1First of two automatic shut-off valves.
- 7Valve provingChecks both shut-off valves for leaks before each start.
- 8Safety shut-off valve 2Second automatic shut-off valve.
- 9High gas pressure switchTrips the burner on over-pressure.
- 10Ratio control valveSets gas flow, linked to the air damper.
- 11Day tankOil storage at the furnace.
- 12StrainerProtects the pump.
- 13Pump setDelivers oil at burner pressure.
- 14Pressure relief valveLimits pressure and returns excess oil.
- 15Oil heaterHeats furnace oil to atomising viscosity. Not needed for LDO.
- 16Oil solenoid valvesAutomatic shut-off on the oil line.
- 17Flow meterMeasures oil consumption.
- 18Oil control valveSets oil flow, linked to air.
- 19Combustion air blowerAir for both fuels; purges the chamber before light-up.
- 20Dual-fuel burnerHigh-velocity burner with gas and oil firing.
At a glance
- Fuels
- NG / LPG · LDO / FO
- Safety
- Double shut-off + proving
- Changeover
- Purge, then switch
- Control
- Burner management PLC
Options, build and uses
Options
- Gas metering
- Remote isolation
- LPG vaporiser connection
How we build it
- Skid fabricated by SHIVAS
- Valves and controls from certified makers
Who it is for
- Galvanizing furnaces
- Dryers
- Annealing and zinc furnaces for wire
Part of
3D model
Computer model from a real SHIVAS project. It shows the arrangement; it is not a photo.
Questions buyers ask
Can one train serve several burners?
A main train can feed branch trains; each burner still needs its own shut-off and control.
From our engineers
Practical notes from the engineers who design and build these plants.